  csm_E5AN-H_e5en-h_ds_e_3_2 1 advanced digital temperature controller E5AN-H/e5en-h (96 x 96 mm and 48 x 96 mm) a new high-performance controller: high resolution, high speed, and high input accuracy. logic operations and preventive maintenance function. plus infrared port on front panel. ? high-resolution display with 5 digits/0.01 c display. ? high-speed sampling cycle of 60 ms. ? high accuracy thermocouple/pt input: 0.1% of pv analog input: 0.1% fs ? universal inputs on all models (thermocouple, pt, or analog input) to handle various sensors with one controller. models also available with remote sp. ? a pv/sv-status display function can be set to automatically alternate between displaying the status of the temperature controller (auto/manual, run/stop, and alarms) and the pv or sv. ? flexible contact outputs with logic operations (and, or, and delays) set from the support software (cx-thermo ver. 4.0) ? preventive maintenance for relays in the temperature controller using a control output on/off counter. ? model available with position-proportional control main i/o functions 96 96 mm E5AN-H 48 96 mm e5en-h refer to safety precautions for e5 @ n/e5 @ n-h . refer to operation for e5 @ n/e5 @ n-h for operating procedures . ? a u to/man u al s w itching ? temperat u re controller stat u s display ? simple program f u nction ? logic operations ? control o u tp u t o n /off co u nt alarm ? p v change rate alarm ? models a v aila b le w ith rs-485, rs-422, or rs-232c comm u nications e v ent inp u ts ? n one ? t w o ? fo u r uni v ersal sensor inp u ts ? uni v ersal thermoco u ple/ pt/analog (c u rrent/ v oltage) inp u ts. indication acc u racy ? thermoco u ple/pt inp u t: 0.1 % of p v ? analog inp u t: 0.1 % fs sampling period ? 60 ms pf key (programma b le key f u nction) a u xiliary o u tp u ts ? t w o ? three remote sp inp u t ? one 3-le v el display sim u ltaneo u sly displays set items, s u ch as the p v , s v , and m v . 5-digit display w ith high resol u tion of 0.01 c infrared port E5AN-H e5en-h comp u ter s u pport soft w are cx-thermo usb control o u tp u t 1 ( bu ilt-in) ? ssr o u tp u ts o u tp u t unit ? relay o u tp u t ? v oltage o u tp u t (for dri v ing ssr) ? c u rrent o u tp u t ? linear v oltage o u tp u t control o u tp u t 2 ( bu ilt-in) ? ssr o u tp u ts o u tp u t unit ? relay o u tp u t ? v oltage o u tp u t (for dri v ing ssr) ? c u rrent o u tp u t ? linear v oltage o u tp u t
E5AN-H/e5en-h 2 lineup note: the controller can be used for heating/cooling co ntrol even if only 1 control output is used. model number structure model number legend controllers 1. type h: advanced 2. control mode blank: standard or heating/cooling control p: position-proportional control 3. control output 1 a: control output unit r: relay output s: ssr output 4. control output 2 a: control output unit r: relay output s: ssr output 5. auxiliary outputs 2: two outputs 3: three outputs 6. option 1 blank: none h: heater burnout/ssr failure/hea ter overcurrent detection (ct1) hh: heater burnout/ssr failure/ heater overcurrent detection (ct2) 7. option 2 b: two event inputs bf: event input + transfer output 8. option 3 m: option unit can be mounted. 9. power supply voltage blank: 100 to 240 vac d: 24 vac/vdc 10.case color blank: black w: silver 11.terminal cover -500: with terminal cover option units 1. function en01: rs-232c communications en02: rs-422 communications en03: rs-485 communications akb: event input output units 1. control output r: relay output q: voltage output (for driving ssr) q3: voltage output (for driving ssr) + 24 vdc (npn) q4: voltage output (for driving ssr) + 24 vdc (pnp) c3: current output + 4 to 20 ma dc c3d: current output + 0 to 20 ma dc v34: linear voltage output + 0 to 10 vdc v35: linear voltage output + 0 to 5 vdc 2. version blank: available for e5an-e5en-h and e5ak/e5ek. n: available only for E5AN-H/e5en-h. E5AN-H/e5en-h advanced type 2 control outputs 1 control output 2 auxiliary outputs 2 auxiliary outputs terminal block fully universal input 1 23456789 11 10 e5an/e5en- @@@@@@@ m @ - @ -500 1 e53- @ 1 2 e53- @@ this data sheet is provided as a guideline fo r selecting products. be sure to refer to the following user manuals for applicati on precautions and other information required for operati on before attempting to use the product. e5cn-h/E5AN-H/e5en-h digital controllers user's manual advanced type (cat. no. h157) e5cn-h/E5AN-H/e5en-h digital controllers comm unications manual advanced type (cat. no. h159)
3 E5AN-H/e5en-h ordering information E5AN-H size case color power supply voltage control method auxiliary output control output 1/2 heater burnout optional functions model event inputs transfer output rsp 1/4 din 96 96 78 (w h d) black 100 to 240 vac basic 2 control output unit 21 2 4 to 20-ma input E5AN-Haa2hbm-500 ssr outputs 212 4 to 20-ma input E5AN-Hss2hbm-500 control output unit 22 2 4 to 20-ma output 4 to 20-ma input E5AN-Haa2hhbfm-500 ssr outputs 222 4 to 20-ma output 4 to 20-ma input E5AN-Hss2hhbfm-500 3 control output unit 22 4 to 20-ma output 4 to 20-ma input E5AN-Haa3bfm-500 ssr outputs 22 4 to 20-ma output 4 to 20-ma input E5AN-Hss3bfm-500 valve 2 relay outputs 22 4 to 20-ma input E5AN-Hprr2bm-500 relay outputs 22 4 to 20-ma output 4 to 20-ma input E5AN-Hprr2bfm-500 24 vac/ vdc basic 2 control output unit 21 2 4 to 20-ma input E5AN-Haa2hbmd-500 ssr outputs 212 4 to 20-ma input E5AN-Hss2hbmd-500 control output unit 22 2 4 to 20-ma output 4 to 20-ma input E5AN-Haa2hhbfmd-500 ssr outputs 222 4 to 20-ma output 4 to 20-ma input E5AN-Hss2hhbfmd-500 3 control output unit 22 4 to 20-ma output 4 to 20-ma input E5AN-Haa3bfmd-500 ssr outputs 22 4 to 20-ma output 4 to 20-ma input E5AN-Hss3bfmd-500 valve 2 relay outputs 22 4 to 20-ma input E5AN-Hprr2bmd-500 relay outputs 22 4 to 20-ma output 4 to 20-ma input E5AN-Hprr2bfmd-500 silver 100 to 240 vac basic 2 control output unit 21 2 4 to 20-ma input E5AN-Haa2hbm-w-500 control output unit 22 2 4 to 20-ma output 4 to 20-ma input E5AN-Haa2hhbfm-w-500 24 vac/ vdc control output unit 21 2 4 to 20-ma input E5AN-Haa2hbmd-w-500
E5AN-H/e5en-h 4 e5en-h accessories (order separately) usb-infrared conversion cable usb-serial conversion cable terminal cover note: the terminal cover comes with the e5cn- @@@ -500 models. waterproof packing note: the waterproof packing is in cluded with the controller. current transformers (cts) cx-thermo support software size case color power supply voltage control method auxil- iary output control output 1/2 heater burn- out optional functions model event inputs transfer output rsp 1/8 din 48 96 78 (w h d) black 100 to 240 vac basic 2 control output unit 21 2 4 to 20-ma input e5en-haa2hbm-500 ssr outputs 212 4 to 20-ma input e5en-hss2hbm-500 control output unit 22 2 4 to 20-ma output 4 to 20-ma input e5en-haa2hhbfm-500 ssr outputs 222 4 to 20-ma output 4 to 20-ma input e5en-hss2hhbfm-500 3 control output unit 22 4 to 20-ma output 4 to 20-ma input e5en-haa3bfm-500 ssr outputs 22 4 to 20-ma output 4 to 20-ma input e5en-hss3bfm-500 valve 2 relay outputs 22 4 to 20-ma input e5en-hprr2bm-500 relay outputs 22 4 to 20-ma output 4 to 20-ma input e5en-hprr2bfm-500 24 vac/vdc basic 2 control output unit 21 2 4 to 20-ma input e5en-haa2hbmd-500 ssr outputs 212 4 to 20-ma input e5en-hss2hbmd-500 control output unit 22 2 4 to 20-ma output 4 to 20-ma input e5en-haa2hhbfmd-500 ssr outputs 222 4 to 20-ma output 4 to 20-ma input e5en-hss2hhbfmd-500 3 control output unit 22 4 to 20-ma output 4 to 20-ma input e5en-haa3bfmd-500 ssr outputs 22 4 to 20-ma output 4 to 20-ma input e5en-hss3bfmd-500 valve 2 relay outputs 22 4 to 20-ma input e5en-hprr2bmd-500 relay outputs 22 4 to 20-ma output 4 to 20-ma input e5en-hprr2bfmd-500 silver 100 to 240 vac basic 2 control output unit 21 2 4 to 20-ma input e5en-haa2hbm-w-500 control output unit 22 2 4 to 20-ma output 4 to 20-ma input e5en-haa2hhbfm-w-500 24 vac/vdc control output unit 21 2 4 to 20-ma input e5en-haa2hbmd-w-500 output unit model specifications relay output e53-rn spst-no, 250 vac, 5 a (resistive load), electrical life: 100,000 operations voltage output (for driving ssr) e53-qn 12 vdc (pnp), max. load current: 40-ma, with short- circuit protection e53-q3 24 vdc (npn), max. load current: 20-ma, with short- circuit protection e53-q4 24 vdc (pnp), max. load current: 20-ma, with short- circuit protection current output e53-c3n 4 to 20-ma dc, load: 600 ? max., resolution: approx. 10,000 e53-c3dn 0 to 20-ma dc, load: 600 ? max., resolution: approx. 10,000 linear voltage output e53-v34n 0 to 10 vdc, load: 1 k ? min., resolution: approx. 10,000 e53-v35n 0 to 5 vdc, load: 1 k ? min., resolution: approx. 10,000 model e58-cifir model e58-cifq1 connectable models model E5AN-H e53-cov16 e5en-h connectable models model E5AN-H y92s-p4 e5en-h y92s-p5 hole diameter model 5.8 dia. e54-ct1 12.0 dia. e54-ct3 model est2-2c-mv4
5 E5AN-H/e5en-h specifications ratings power supply voltage no d in model number: 100 to 240 vac, 50/60 hz d in model number: 24 vac, 50/60 hz; 24 vdc operating voltage range 85% to 110% of rated supply voltage power consumption 100 to 240 vac: 12 va 24 vac/vdc: 8.5 va (24 vac)/5.5 w (24 vdc) sensor input any of the following can be selected. thermocouple: k, j, t, e, l, u, n, r, s, b, w, or pl ii platinum resistance thermometer: pt100 or jpt100 current input: 4 to 20 ma or 0 to 20 ma voltage input: 1 to 5 v, 0 to 5 v, or 0 to 10 v input impedance current input: 150 ? max., voltage input: 1 m ? min. (use a 1:1 connection when connecting the es2-hb.) control method on/off control or 2-pid control (with auto-tuning) control output relay output output unit (install the out put unit (sold separately).) voltage output (for driving ssr) current output linear voltage output built-in ssr output 75 to 250 vac, 1 a (resistive load) relay output for position-proportional control relay output: open and close: spst-no, 250 vac, 1 a (including in-rush current), electrical life: 100,000 operations min. potentiometer input: must be between 100 ? and 2.5 k ? for maximum open position. auxiliary output number of outputs 2 or 3 max. output specifications relay output: spst-no, 250 vac, 3 a (resistive load), electric al life: 100,000 operations, minimum applicable load: 5 v, 10 ma event input number of outputs 2 or 4 (with an e53-akb) external contact input specifications contact input: on: 1 k ? max., off: 100 k ? min. non-contact input: on: residual voltage: 1.5 v max., off: leakage current: 0.1 ma max. current flow: approx. 7 ma per contact logic operations number of operations 8 max. operations ? logic operation: any of the following four patterns can be selected. the input status may be inverted. (a and b) or (c and d), (a or c) and (b or d), a or b or c or d, a and b and c and d (a, b, c, and d are four inputs.) ? delay: on delay or off delay for the results of the logic operation given above. setting time: 0 to 9999 s or 0 to 9999 min ? output inversion: possible output one work bit per operation work bit assignment any of the following can be assigned to up to eight work bits (logic operation results): event input operations, auxiliary outputs, or control outputs. transfer outputs number of outputs 1 max. (depends on model. models with transfer output (f in model number) output specifications current output: 4 to 20 ma dc, load: 600 ? max., resolution at 4 to 20 ma: approx. 10,000 rsp input number of inputs 1 signal type current input: 4 to 20 ma (input impedance: 150 ? 10%) analog input scaling scaling of signal to engineering units (eu) ? 19,999 to 30,000 (display: 30,000 max.) accuracy ( 0.2% of fs) 1 digit max. input sampling period 60 ms setting method set digitally using keys on the front panel or by using the rsp input. indication method 11-segment digital display and individual indi cators (7-segments displays also possible) character height: E5AN-H: pv: 15.8 mm, sv: 9.5 mm, mv: 6.8 mm; e5en-h: pv: 11.8 mm, sv: 8.1 mm, mv: 5.8 mm content of 3-level display: pv/sv/mv, pv/sv/bank no., or soak time remain number of digits: 5 for pv and sv, 4 for mv bank switching supported (number of banks: 8) local sp, alarm settings, pid sets (pid constants, mv upper limit, mv lower limit, etc.) other functions manual output, heating/cooling control, loop burnout alarm, sp ramp, other alarm functions, heater burnout detection, 40% at, 100% at, mv limiter, input digital filter, self-tuning, tem perature input shift, run/stop, protection functions, control ou tput on/off counter, extraction of square root, mv change rate limit , pv/sv status display, logic operations, automatic cooling coefficient adjustment ambient operating temperature ? 10 to 55 c (with no condensation or icing), for 3-year warranty: ? 10 to 50 c ambient operating humidity 25% to 85% storage temperature ? 25 to 65 c (with no condensation or icing)
E5AN-H/e5en-h 6 input ranges thermocouple/platinum r esistance thermometer (fully universal inputs) input type platinum resistance thermometer thermocouple analog input name pt100 jpt100 k j t e l u n r s b w pl ii 4 to 20 m a 0 to 20 m a 1 to 5v 0 to 5v 0 to 10 v temperature range ( c) 2300 1800 1700 1600 1500 1400 1300 1200 1100 1000 900 800 700 600 500 400 300 200 100 0 ? 100.0 ? 200.0 2300.0 usable in the following ranges by scaling: ? 19999 to 32400, ? 1999.9 to 3240.0, ? 199.99 to 324.00, or ? 19.999 to 32.400 1800.0 1700.01700.0 1300.0 1300.0 1300.0 850.0 850.0 850.0 600.0 500.0 500.0 500.0 400.0 400.0 400.0 400.0 400.0 200.00 200.00 200.00 200.00 100.0 100.0 100.0 0.0 0.0 0.0 0.0 0.0 0.0 ? 50.00 ? 20.0 ? 50.00 ? 100.0 ? 20.0 ? 50.00 ? 50.00 ? 100.0 ? 200.0 ? 199.9 ? 199.9 ? 200.0 ? 200.0 ? 199.9 ? 200.0 ? 200.0 ? 199.9 ? 200.0 setting number 0122434 5 6 21 7 8 22 9 102311121314151617181920 25 26 27 28 29 shaded settings are the default settings. the applicable standards for the input types are as follows: k, j, t, e, n, r, s, b: jis c 1602-1995, iec 584-1 l: fe-cuni, din 43710-1985 u: cu-cuni, din 43710-1985 w: w5re/w26re, astm e988-1990 jpt100: jis c 1604-1989, jis c 1606-1989 pt100: jis c 1604-1997, iec 751 pl ii: according to platinel ii electromotive force charts from basf (previously engelhard)
7 E5AN-H/e5en-h alarm outputs each alarm can be independently set to one of the following 13 alarm types. the default is 2: upper limit . auxiliary outputs are allocated for alarms. on delays and off delays (0 to 999 s) can also be specified. note: for models with heater burnout, ssr failure, and heater overcurrent detection, alarm 1 will be an or output of the alarm select ed from the following alarm types and the alarms for heater burnout, ssr failure, and heater overcurrent. to output only a heater burnout a larm, ssr failure alarm, and heater overcurrent alarm for alarm 1, set the alarm type to 0 (i.e., no alarm function). *1. with set values 1, 4 and 5, t he upper and lower limit values can be set independently for each alar m type, and are expressed as ?l? and ?h.? *2. set value: 1, upper- and lower-limit alarm *3. set value: 4, upper- and lower-limit range *4. set value: 5, upper- and lower-limit with standby sequence for upper- and lower-limit alarm described above ? case 1 and 2 always off when the upper-limit and lower-limit hysteresis overlaps. ? case 3: always off *5. set value: 5, upper- and lower-limit with standby sequence always off when the upper-limit and lower-limit hysteresis overlaps. *6. displayed when there is a remote sp input. *7. refer to the e5cn/e5an/e5en/e5gn digital temperature controllers user's manual basic type (cat. no. h156) for information on the operation of the standby sequence. *8. refer to the e5cn/e5an/e5en/e5gn digital temperature controllers user's manual basic type (cat. no. h156) for information on the loop burnout alarm (lba). *9. refer to the e5cn/e5an/e5en/e5gn digital temperature controllers user's manual basic type (cat. no. h156) for information on the pv change rate alarm. set value alarm type alarm output operation description of function when alarm value x is positive when alarm value x is negative 0 alarm function off output off no alarm 1 upper- and lower-limit * 1 * 2 set the deviation in the set point by setting the alarm upper limit (h) and alarm lower limit (l). 2 upper-limit set the upward deviation in the set point by setting the alarm value (x). 3 lower-limit set the downward deviation in the set point by setting the alarm value (x). 4 upper- and lower-limit range * 1 * 3 set the deviation in the set point by setting the alarm upper limit (h) and alarm lower limit (l). 5 upper- and lower-limit with standby sequence * 1 * 5 * 4 a standby sequence is added to the upper- and lower-limit alarm (1). * 7 6 upper-limit with standby sequence a standby sequence is added to the upper-limit alarm (2). * 7 7 lower-limit with standby sequence a standby sequence is added to the lower-limit alarm (3). * 7 8 absolute-value upper-limit the alarm will turn on if the process value is larger than the alarm value (x) regardless of the set point. 9 absolute-value lower-limit the alarm will turn on if the process value is smaller than the alarm value (x) regardless of the set point. 10 absolute-value upper-limit with standby sequence a standby sequence is added to the absolute-value upper-limit alarm (8). * 7 11 absolute-value lower-limit with standby sequence a standby sequence is added to the absolute-value lower-limit alarm (9). * 7 12 lba (alarm 1 type only) --- * 8 13 pv change rate alarm --- * 9 14 rsp absolute value upper limit * 6 the alarm turns on when the remote sp (rsp) is larger than the alarm value (x ). this alarm functions in both local sp and remote sp modes. 15 rsp absolute value lower limit * 6 the alarm turns on when the remote sp (rsp) is smaller than the alarm value (x). this alarm functions in both local sp and remote sp modes. o n off sp lh sp x o n off sp x o n off sp x o n off sp x o n off sp lh o n off sp lh o n off sp x o n off sp x o n off sp x o n off sp x o n off 0 x o n off 0 x o n off 0 x o n off 0 x o n off 0 x o n off 0 x o n off 0 x o n off 0 x o n off 0 x o n off 0 x o n off 0 x o n off 0 x o n off lh h < 0, l > 0 ? h ? < ? l ? sp case 1 lh h > 0, l < 0 ? h ? > ? l ? sp case 2 l h h < 0, l < 0 sp l h h < 0, l > 0 ? h ? ? l ? sp l h h > 0, l < 0 ? h ? ? l ? sp case 3 (al w ays o n ) lh h < 0, l > 0 ? h ? < ? l ? sp case 1 lh h > 0, l < 0 ? h ? > ? l ? sp case 2 l h h < 0, l < 0 sp l h h < 0, l > 0 ? h ? ? l ? sp l h h > 0, l < 0 ? h ? ? l ? sp case 3 (al w ays o n )
E5AN-H/e5en-h 8 characteristics *1. the indication accuracy of k thermocouples in the ? 200 to 1300 c range, t and n thermocouples at a temperature of ? 100 c max., and u and l thermocouples at any temperatures is 2 c 1 digit max. the indication accuracy of t he b thermocouple at a temperature of 400 c max. is not specified. the indication accuracy of b thermocouples in the 400 to 800 c range is 3 c max. the indication accuracy of the r and s thermocouples at a temperature of 200 c max. is 3 c 1 digit max. the indication accu racy of w thermocouples is 0.3% of pv or 3 c, whichever is greater, 1 digit max. the indication accuracy of pl ii thermocouples is 0.3% of pv or 2 c, whichever is greater, 1 digit max. *2. ambient temperature: ? 10 c to 23 c to 55 c, voltage range: ? 15% to 10% of rated voltage *3. k thermocouple at ? 100 c max.: 10 c max. *4. external communications (rs-232c, rs-485, or rs-422) and c able communications for the setup t ool can be used at the same time. *5. refer to information on maritime standards in safety precautions for e5 @ n/e5 @ n-h for compliance with lloyd's standards. indication accuracy thermocouple: ( 0.1% of indicated value or 1 c, whichever is greater) 1 digit max. * 1 platinum resistance thermometer: ( 0.1% of indicated value or 0.5 c, whichever is greater) 1 digit max. analog input: 0.1% fs 1 digit max. ct input: 5% fs 1 digit max. potentiometer input: 5% fs 1 digit max. transfer output accuracy 0.3% fs max. influence of temperature * 2 thermocouple input (r, s, b, w, pl ii): ( 1% of pv or 10 c, whichever is greater) 1 digit max. other thermocouple input: ( 1% of pv or 4 c, whichever is greater) 1 digit max. * 3 platinum resistance thermometer: ( 1% of pv or 2 c, whichever is greater) 1 digit max. analog input: ( 1%fs) 1 digit max. influence of voltage * 2 input sampling period 60 ms hysteresis temperature input: 0.1 to 3240.0 c or f (in units of 0.1 c or f) analog input: 0.01% to 99.99% fs (in units of 0.01% fs) proportional band (p) temperature input: 0.1 to 3240.0 c or f (in units of 0.1 c or f) analog input: 0.1% to 999.9% fs (in units of 0.1% fs) integral time (i) 0.0 to 3240.0 s (in units of 0.1 s) derivative time (d) 0.0 to 3240.0 s (in units of 0.1 s) control period 0.5, 1 to 99 s (in units of 1 s) manual reset value 0.0 to 100.0% (in units of 0.1%) alarm setting range ? 19999 to 32400 (decimal point position depends on input type) affect of signal source resistance thermocouple: 0.1 c/ max. (100 max.) platinum resistance thermometer: 0.1 c/ max. (10 max.) insulation resistance 20 m min. (at 500 vdc) dielectric strength 2,300 vac, 50 or 60 hz for 1 min (b etween terminals with different charge) vibration resistance malfunction 10 to 55 hz, 20 m/s 2 for 10 min each in x, y, and z directions destruction 10 to 55 hz, 0.75-mm single amplitude for 2 hrs each in x, y, and z directions shock resistance malfunction 100 m/s 2 , 3 times each in x, y, and z directions destruction 300 m/s 2 , 3 times each in x, y, and z directions weight E5AN-H controller: approx. 310 g, m ounting bracket: approx. 100 g e5en-h controller: approx. 260 g, m ounting bracket: approx. 100 g degree of protection front panel: ip66, rear case: ip20, terminals: ip00 memory protection non-volatile memory (number of writes: 1,000,000 times) setup tool cx-thermo version 4.0 or higher setup tool port provided on the bottom of the E5AN-H and e5en-h. an e58-cifq1 usb-serial co nversion cable is required to connect the computer to the E5AN-H and e5en-h. provided on the front of the E5AN-H and e5en-h. an e 58-cifir usb-infrared conver sion cable is required to connect the computer to the E5AN-H or e5en-h. * 4 standards approved standards ul 61010-1, csa c22.2 no. 1010-1 conformed standards en 61010-1 (iec 61010-1): pollution level 2, overcurrent category ii, lloyd's standards * 5 emc emi: en 61326 radiated interference electromagnetic fi eld strength: en 55011 group 1, class a noise terminal voltage: en 55011 group 1, class a ems: en 61326 esd immunity: en 61000-4-2 electromagnetic field im munity: en 61000-4-3 burst noise immunity: en 61000-4-4 conducted disturbance immunity: en 61000-4-6 surge immunity: en 61000-4-5 power frequency magnetic fiel d immunity: en 61000-4-8 voltage dip/interrupting immunity: en 61000-4-11
9 E5AN-H/e5en-h usb-serial conversion cable note: a driver must be installed in the personal computer. refer to installation information in the operation manual for the conversion cable. communications specifications * the baud rate, data bit length, stop bit length, and vertical parity can be individually set using the communications setting level. current transformer (order separately) ratings usb-infrared conversion cable note: a driver must be installed in the personal computer. refer to installation information in the operation manual for the conversion cable. heater burnout alarms, ssr failure alarms, and heater overcurrent alarms *1. for heater burnout alarms, the heater current will be measured when the control output is on, and the output assigned to the alarm 1 function will turn on if the heater current is lower than the set value (i.e., heater burnout detection current value). *2. for ssr failure alarms, the heater current will be measured when the control output is off, and t he output assigned to the alarm 1 function will turn on if the hea ter current is higher than the set value (i.e., ssr failure det ection current value). *3. for heater overcurrent alarms, the heater current will be measured when the control output is on, and the output assigned to the alarm 1 function will turn on if the heater current is higher than the set value (i.e., heater overcurrent detection current value). applicable os windows 2000, xp, or vista applicable software cx-thermo version 4 or higher applicable models e5an/e5en/e5cn/e5cn-u/ E5AN-H/e5en-h/e5cn-h/e5gn usb interface standard conforms to usb specification 1.1. dte speed 38400 bps connector specifications computer: usb (type a plug) temperature controller: setup tool port (on bottom of controller) power supply bus power (supplied from usb host controller.) power supply voltage 5 vdc current consumption 70 ma ambient operating temperature 0 to 55c (with no condensation or icing) ambient operating humidity 10% to 80% storage temperature ? 20 to 60c (with no condensation or icing) storage humidity 10% to 80% altitude 2,000 m max. weight approx. 100 g transmission line connection method rs-485, rs-422: multipoint rs-232c: point-to-point communications rs-485 (two-wire, half duplex) rs-422 (four-wire, half duplex) or rs-232c synchronization method start-stop synchronization protocol compoway/f, sysway, or modbus baud rate 1200, 2400, 4800, 9600, 19200, 38400, or 57600 bps transmission code ascii (compoway/f, sysway) rtu (modbus) data bit length * 7 or 8 bits stop bit length * 1 or 2 bits error detection vertical parity (none, even, odd) frame check sequence (fcs) with sysway block check charac ter (bcc) with compoway/f or crc-16 modbus flow control none interface rs-485, rs-422, or rs-232c retry function none communications buffer 217 bytes communications response wait time 0 to 99 ms default: 20 ms dielectric strength 1,000 vac for 1 min vibration resistance 50 hz, 98 m/s 2 weight e54-ct1: approx. 11.5 g, e54-ct3: approx. 50 g accessories (e54-ct3 only) armatures (2) plugs (2) applicable os windows 2000, xp, or vista applicable software cx-thermo version 4.0 or higher applicable models E5AN-H/e5en-h usb interface standard conforms to usb specification 1.1. dte speed 38400 bps connector specifications computer: usb (type a plug) temperature controller: infrared port (on front of controller) power supply bus power (supplied from usb host controller.) power supply voltage 5 vdc current consumption 80 ma ambient operating temperature 0 to 55c (with no condensation or icing) ambient operating humidity 10% to 80% storage temperature ? 20 to 60c (with no condensation or icing) storage humidity 10% to 80% altitude 2,000 m max. weight approx. 130 g (with mounting adaptor) ct input (for heater current detection) models with detection for single-phase heaters: one input models with detection for single-phase or three-phase heaters: two inputs maximum heater current 50 a ac input current indication accuracy 5% fs 1 digit max. heater burnout alarm setting range * 1 0.1 to 49.9 a (in units of 0.1 a) minimum detection on time: 100 ms ssr failure alarm setting range * 2 0.1 to 49.9 a (in units of 0.1 a) minimum detection off time: 100 ms heater overcurrent alarm setting range * 3 0.1 to 49.9 a (in units of 0.1 a) minimum detection on time: 100 ms
E5AN-H/e5en-h 10 electrical life expectancy curve for relays (reference values) ssr outputs (out1/out2) ratings ? rated load voltage: 75 to 250 vac ? rated load current: 1 a (resistive load) note: 1. the load current must be within the derating curve. 2. there is no zero-cross function. derating curve for ssr outputs (reference values) condition a: ssr outputs 100% on condition b: ssr outputs 50% on with 2-s control cycle 500 300 100 50 30 10 5 3 1 0123456 E5AN-H/e5en-h 250 vac, 30 vdc (resistive load) cos = 1 switching current (a) life ( 10 4 operations) 1.5 1.25 1 0.75 0.5 0.25 0 ? 10 0 10 20 30 40 50 55 45 60 ambient temperature ( c) load current i (a) out1/out2 condition a condition b
11 E5AN-H/e5en-h external connections control output 1 and control output 2 are functi onally isolated from t he internal circuits. note: wire all voltage input terminals correctly. the controller may fail if voltage input terminals are wired incorrectly. potentiometer rdb rda sg sdb sda 4 to 20 ma dc (load: 600 max.) 4 to 20 ma dc 1 2 3 4 5 6 7 8 9 10 21 22 23 24 25 26 27 28 29 30 21 22 23 24 25 26 27 28 29 30 11 12 13 14 15 16 17 18 19 20 ? 100 to 240 vac ? 24 vac/vdc (no polarity) inp u t po w er s u pply control o u tp u t 1 b v ma control o u tp u t 2 ct2 ct1 ev1 ev2 ct2 do not use do not use do not use b a c w o do not use do not use do not use do not use e v ent inp u ts ev1 ev2 e v ent inp u ts comm u nications b ( + ) a ( ? ) do not use b ( + ) a ( ? ) 11 12 13 21 22 e53-en03 rs-485 11 12 13 21 22 e53-en01 rs-232c sd rd sg do not use do not use 11 12 13 21 22 e53-akb 11 12 13 21 22 e53-en02 rs-422 control o u tp u t unit control o u tp u ts 1, 2 refer to page 4 ssr o u tp u ts 75 to 250 vac, 1 a (resisti v e load) models w ith position- proportional control relay o u tp u t 250 vac, 1 a (incl u ding inr u sh c u rrent) control o u tp u ts 1, 2 relay o u tp u t spst-no, 250 vac, 3 a (resisti v e load) a u xiliary o u tp u ts 1, 2, 3 a heater b u rno u t alarm, ssr fail u re, heater o v erc u rrent alarm, inp u t alarm, or remote sp inp u t error is sent to the o u tp u t to w hich the alarm 1 f u nction is assigned. a u xiliary o u tp u t 3 14 15 16 1 2 3 4 5 6 7 8 9 10 21 22 23 24 25 26 27 28 29 30 ev4 ev3 + ? + ? + ? + ? o u tp u t u nit o u tp u t u nit control o u tp u t unit 1 2 3 4 5 6 7 8 9 10 ssr ssr ssr o u tp u ts 1 2 3 4 5 6 7 8 9 10 open closed models w ith position- proportional control e v ent inp u t/ transfer o u tp u t/ remote sp remote sp inp u t do not use transfer o u tp u t inp u t po w er s u pply inp u t po w er s u pply inp u t po w er s u pply a u xiliary o u tp u t 2 a u xiliary o u tp u t 1 a u xiliary o u tp u t 2 a u xiliary o u tp u t 1 a u xiliary o u tp u t 2 a u xiliary o u tp u t 1 a u xiliary o u tp u t 2 a u xiliary o u tp u t 1 relay o u tp u t spdt, 250 vac, 3 a (resisti v e load) a u xiliary o u tp u t 3 the temperat u re controller is set for a k-type thermoco u ple (inp u t type = 5) by defa u lt. an inp u t error ( s.err ) w ill occ u r if the inp u t type setting does not agree w ith the temperat u re sensor. check the inp u t type. option units controllers
E5AN-H/e5en-h 12 nomenclature dimensions (unit: mm) pf a/m sub3 ha sub2 out2 out1 cmw rsp stop manu sub1 mv sv pv ir E5AN-H operation indicators no.1 display no.2 display no.3 display up key down key temperature unit mode key level key programmable function key/ auto/manual key E5AN-H e5en-h ir pf a/m mv sv pv sub2 sub3 stop out1 rsp manu cmw out2 sub1 ha e5en-h operation indicators temperature unit operation indicators mode key level key no.1 display no.2 display no.3 display up key down key programmable function key/ auto/manual key mounting bracket (accessory) waterproof packing (accessory) terminal cover (e53-cov16) (accessory) crimp terminal size: m3.5 96 96 112 91 79.2 6 2 92 +0.8 0 92 +0.8 0 92 +0.8 0 (96 number of units ? 3.5) +1.0 0 120 min. group mounting does not allow waterproofing. mounted separately group mounted * ? recommended panel thickness is 1 to 8mm. ? group mounting is not possible in the vertical direction. (maintain the specified mounting space between controllers.) ? to mount the controller so that it is waterproof, insert the waterproof packing onto the controller. ? when two or more controllers are mounted, make sure that the surrounding temperature does not exceed the allowable operating temperature specified in the specifications. E5AN-H * group mounting is not possible if an ssr output is used for control output 1 or 2 and the e53-c3n or e53-c3dn output unit is used. for these combinations, maintain the following mounting space between controllers. 92 +0.8 0 92 +0.8 0 110 min. 120 min.
13 E5AN-H/e5en-h mounting bracket (accessory) waterproof packing (accessory) terminal cover (e53-cov16) (accessory) crimp terminal size: m3.5 96 112 48 79.2 6 91 2 e5en-h 92 +0.8 0 92 +0.8 0 45 +0.6 0 120 min. (48 number of units ? 2.5) +1.0 0 group mounting does not allow waterproofing. mounted separately group mounted * ? recommended panel thickness is 1 to 8 mm. ? group mounting is not possible in the vertical direction. (maintain the specified mounting space between controllers.) ? when two or more controllers are mounted, make sure that the surrounding temperature does not exceed the allowable operating temperature specified in the specifications. * group mounting is not possible if an ssr output is used for control output 1 or 2 and the e53-c3n or e53-c3dn output unit is used. for these combinations, maintain the following mounting space between controllers. 45 +0.6 0 60 min. 120 min. 92 +0.8 0
E5AN-H/e5en-h 14 accessories (order separately) (2,000) 54 4.6 dia. 35.8 17.8 usb connector (type a plug) led indicator: rd led indicator: sd usb-infrared conversion cable e58-cifir usb-infrared conversion cable 16 99.2 18.5 23.1 (75) 21.8 39 mounting adapter (accessory) with mounting adapter connected mounting adapter (2,100) 250 1,765 usb connector (type a plug) serial connecto r led indicator: rd led indicator: sd usb-serial conversion cable e58-cifq1 terminal covers e53-cov16 (six covers provided.) 10 1.2 3.2 44.8
15 E5AN-H/e5en-h current transformers waterproof packing y92s-p4 (for din 96 96) order the waterproof packing separately if it becomes lost or damaged. the waterproof packing can be used to achieve an ip66 degree of protection. (deterioration, shrinking, or harde ning of the waterproof packing may occur depending on the operating env ironment. therefore, periodic replacement is recommended to ensure the level of waterproofing specified in ip66. the time for periodic replacement depends on the operating environment. be sure to c onfirm this point at your site. consider one year a rough standard. omron shall not be liable for the level of water resistance if the customer does not perform periodic replacement.) the waterproof packing does not need to be attached if a waterproof structure is not required. y92s-p5 (for din 48 96) e54-ct3 accessory ? armature 30 21 15 5.8 dia. 25 3 40 10.5 2.8 7.5 10 two, 3.5 dia. 40 40 30 12 dia. 9 2.36 dia. 15 30 two, m3 (depth 4) approx. 3 dia. 18 (22) approx. 6 dia. plug armature lead e54-ct1 e54-ct3 connection example ? plug e54-ct1 thru-current (io) vs. output voltage (eo) (reference values) maximum continuous heater current: 50 a (50/60 hz) number of windings: 400 2 winding resistance: 18 2 ? thru-current (io) a (r.m.s.) 1 10 100 ma 1 10 100 1,000 a output voltage (eo) v (r.m.s.) 100 v 50 hz distortion factor 10% 3% 1% 100 ? r l = 10 ? 10 1 100 mv 10 1 100 v 10 1 k ? e54-ct3 thru-current (io) vs. output voltage (eo) (reference values) maximum continuous heater current: 120 a (50/60 hz) (maximum continuous heater current for an omron temperature controller is 50 a.) number of windings: 4002 winding resistance: 80.8 ? 3% 1% 1 k ? 100 ? 50 ? r l = 10 ? 500 ? distor- tion factor 10% thru-current (io) a (r.m.s.) 1 10 100 ma 1 10 100 1,000 a output voltage (eo) v (r.m.s.) 100 v 50 hz 10 1 100 mv 10 1 100 v 10
r e a d a n d u n d e r s t a n d t h i s c a t a l o g p l e a s e r e a d a n d u n d e r s t a n d t h i s c a t a l o g b e f o r e p u r c h a s i n g t h e p r o d u c t s . p l e a s e c o n s u l t y o u r o m r o n r e p r e s e n t a t i v e i f y o u h a v e a n y q u e s t i o n s o r c o m m e n t s . w a r r a n t y a n d l i m i t a t i o n s o f l i a b i l i t y w a r r a n t y o m r o n ' s e x c l u s i v e w a r r a n t y i s t h a t t h e p r o d u c t s a r e f r e e f r o m d e f e c t s i n m a t e r i a l s a n d w o r k m a n s h i p f o r a p e r i o d o f o n e y e a r ( o r o t h e r p e r i o d i f s p e c i f i e d ) f r o m d a t e o f s a l e b y o m r o n . o m r o n m a k e s n o w a r r a n t y o r r e p r e s e n t a t i o n , e x p r e s s o r i m p l i e d , r e g a r d i n g n o n - i n f r i n g e m e n t , m e r c h a n t a b i l i t y , o r f i t n e s s f o r p a r t i c u l a r p u r p o s e o f t h e p r o d u c t s . a n y b u y e r o r u s e r a c k n o w l e d g e s t h a t t h e b u y e r o r u s e r a l o n e h a s d e t e r m i n e d t h a t t h e p r o d u c t s w i l l s u i t a b l y m e e t t h e r e q u i r e m e n t s o f t h e i r i n t e n d e d u s e . o m r o n d i s c l a i m s a l l o t h e r w a r r a n t i e s , e x p r e s s o r i m p l i e d . l i m i t a t i o n s o f l i a b i l i t y o m r o n s h a l l n o t b e r e s p o n s i b l e f o r s p e c i a l , i n d i r e c t , o r c o n s e q u e n t i a l d a m a g e s , l o s s o f p r o f i t s o r c o m m e r c i a l l o s s i n a n y w a y c o n n e c t e d w i t h t h e p r o d u c t s , w h e t h e r s u c h c l a i m i s b a s e d o n c o n t r a c t , w a r r a n t y , n e g l i g e n c e , o r s t r i c t l i a b i l i t y . i n n o e v e n t s h a l l t h e r e s p o n s i b i l i t y o f o m r o n f o r a n y a c t e x c e e d t h e i n d i v i d u a l p r i c e o f t h e p r o d u c t o n w h i c h l i a b i l i t y i s a s s e r t e d . i n n o e v e n t s h a l l o m r o n b e r e s p o n s i b l e f o r w a r r a n t y , r e p a i r , o r o t h e r c l a i m s r e g a r d i n g t h e p r o d u c t s u n l e s s o m r o n ' s a n a l y s i s c o n f i r m s t h a t t h e p r o d u c t s w e r e p r o p e r l y h a n d l e d , s t o r e d , i n s t a l l e d , a n d m a i n t a i n e d a n d n o t s u b j e c t t o c o n t a m i n a t i o n , a b u s e , m i s u s e , o r i n a p p r o p r i a t e m o d i f i c a t i o n o r r e p a i r . a p p l i c a t i o n c o n s i d e r a t i o n s s u i t a b i l i t y f o r u s e o m r o n s h a l l n o t b e r e s p o n s i b l e f o r c o n f o r m i t y w i t h a n y s t a n d a r d s , c o d e s , o r r e g u l a t i o n s t h a t a p p l y t o t h e c o m b i n a t i o n o f p r o d u c t s i n t h e c u s t o m e r ' s a p p l i c a t i o n o r u s e o f t h e p r o d u c t s . a t t h e c u s t o m e r ' s r e q u e s t , o m r o n w i l l p r o v i d e a p p l i c a b l e t h i r d p a r t y c e r t i f i c a t i o n d o c u m e n t s i d e n t i f y i n g r a t i n g s a n d l i m i t a t i o n s o f u s e t h a t a p p l y t o t h e p r o d u c t s . t h i s i n f o r m a t i o n b y i t s e l f i s n o t s u f f i c i e n t f o r a c o m p l e t e d e t e r m i n a t i o n o f t h e s u i t a b i l i t y o f t h e p r o d u c t s i n c o m b i n a t i o n w i t h t h e e n d p r o d u c t , machin e , s y s t e m , o r o t h e r a p p l i c a t i o n o r u s e . t h e f o l l o w i n g a r e s o m e e x a m p l e s o f a p p l i c a t i o n s f o r w h i c h p a r t i c u l a r a t t e n t i o n m u s t b e g i v e n . t h i s i s n o t i n t e n d e d t o b e a n e x h a u s t i v e l i s t o f a l l p o s s i b l e u s e s o f t h e p r o d u c t s , n o r i s i t i n t e n d e d t o i m p l y t h a t t h e u s e s l i s t e d m a y b e s u i t a b l e f o r t h e p r o d u c t s : o u t d o o r u s e , u s e s i n v o l v i n g p o t e n t i a l c h e m i c a l c o n t a m i n a t i o n o r e l e c t r i c a l i n t e r f e r e n c e , o r c o n d i t i o n s o r u s e s n o t d e s c r i b e d i n t h i s c a t a l o g . n u c l e a r e n e r g y c o n t r o l s y s t e m s , c o m b u s t i o n s y s t e m s , r a i l r o a d s y s t e m s , a v i a t i o n s y s t e m s , m e d i c a l e q u i p m e n t , a m u s e m e n t m a c h i n e s , v e h i c l e s , s a f e t y e q u i p m e n t , a n d i n s t a l l a t i o n s s u b j e c t t o s e p a r a t e i n d u s t r y o r g o v e r n m e n t r e g u l a t i o n s . s y s t e m s , m a c h i n e s , a n d e q u i p m e n t t h a t c o u l d p r e s e n t a r i s k t o l i f e o r p r o p e r t y . p l e a s e k n o w a n d o b s e r v e a l l p r o h i b i t i o n s o f u s e a p p l i c a b l e t o t h e p r o d u c t s . n e v e r u s e t h e p r o d u c t s f o r a n a p p l i c a t i o n i n v o l v i n g s e r i o u s r i s k t o l i f e o r p r o p e r t y w i t h o u t e n s u r i n g t h a t t h e s y s t e m a s a w h o l e h a s b e e n d e s i g n e d t o a d d r e s s t h e r i s k s , a n d t h a t t h e o m r o n p r o d u c t s a r e p r o p e r l y r a t e d a n d i n s t a l l e d f o r t h e i n t e n d e d u s e w i t h i n t h e o v e r a l l e q u i p m e n t o r s y s t e m . p r o g r a m m a b l e p r o d u c t s o m r o n s h a l l n o t b e r e s p o n s i b l e f o r t h e u s e r ' s p r o g r a m m i n g o f a p r o g r a m m a b l e p r o d u c t , o r a n y c o n s e q u e n c e t h e r e o f . d i s c l a i m e r s c h a n g e i n s p e c i f i c a t i o n s p r o d u c t s p e c i f i c a t i o n s a n d a c c e s s o r i e s m a y b e c h a n g e d a t a n y t i m e b a s e d o n i m p r o v e m e n t s a n d o t h e r r e a s o n s . i t i s o u r p r a c t i c e t o c h a n g e m o d e l n u m b e r s w h e n p u b l i s h e d r a t i n g s o r f e a t u r e s a r e c h a n g e d , o r w h e n s i g n i f i c a n t c o n s t r u c t i o n c h a n g e s a r e m a d e . h o w e v e r , s o m e s p e c i f i c a t i o n s o f t h e p r o d u c t s m a y b e c h a n g e d w i t h o u t a n y n o t i c e . w h e n i n d o u b t , s p e c i a l m o d e l n u m b e r s m a y b e a s s i g n e d t o f i x o r e s t a b l i s h k e y s p e c i f i c a t i o n s f o r y o u r a p p l i c a t i o n o n y o u r r e q u e s t . p l e a s e c o n s u l t w i t h y o u r o m r o n r e p r e s e n t a t i v e a t a n y t i m e t o c o n f i r m a c t u a l s p e c i f i c a t i o n s o f p u r c h a s e d p r o d u c t s . d i m e n s i o n s a n d w e i g h t s d i m e n s i o n s a n d w e i g h t s a r e n o m i n a l a n d a r e n o t t o b e u s e d f o r m a n u f a c t u r i n g p u r p o s e s , e v e n w h e n t o l e r a n c e s a r e s h o w n . p e r f o r m a n c e d a t a perfor m a n c e d a t a g i v e n i n t h i s c a t a l o g i s p r o v i d e d a s a g u i d e f o r t h e u s e r i n d e t e r m i n i n g s u i t a b i l i t y a n d d o e s n o t c o n s t i t u t e a w a r r a n t y . i t m a y r e p r e s e n t t h e r e s u l t o f o m r o n ? s t e s t c o n d i t i o n s , a n d t h e u s e r s m u s t c o r r e l a t e i t t o a c t u a l a p p l i c a t i o n r e q u i r e m e n t s . a c t u a l p e r f o r m a n c e i s s u b j e c t t o t h e o m r o n w a r r a n t y a n d l i m i t a t i o n s o f l i a b i l i t y . e r r o r s a n d o m i s s i o n s t h e i n f o r m a t i o n i n t h i s d o c u m e n t h a s b e e n c a r e f u l l y c h e c k e d a n d i s b e l i e v e d t o b e a c c u r a t e ; h o w e v e r , n o r e s p o n s i b i l i t y i s a s s u m e d f o r c l e r i c a l , t y p o g r a p h i c a l , o r p r o o f r e a d i n g e r r o r s , o r o m i s s i o n s . 2009 . 1 1 i n t h e i n t e r e s t o f p r o d u c t i m p r o v e m e n t , s p e c i f i c a t i o n s a r e s u b j e c t t o c h a n g e w i t h o u t n o t i c e . o m r o n c o r p o r a t i o n i n d u s t r i a l a u t o m a t i o n c o m p a n y h t t p : / / w w w . i a . o m r o n . c o m / ( c ) c o p y r i g h t o m r o n c o r p o r a t i o n 2 0 0 9 a l l r i g h t r e s e r v e d .


▲Up To Search▲   

 
Price & Availability of E5AN-H

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X